Does a HVAC Boiler Need Glycol? (Running a Boiler with No Glycol)

masthead-logo-icon
Does a HVAC Boiler Need Glycol?
(Running a Boiler With No Glycol)

A boiler can run without glycol; it will heat water and function normally. In fact, water is more efficient at heat transfer than glycol. So why even feed glycol in a boiler system? A boiler heats to temperatures significantly above freezing; however, there is still some risk that it could freeze. If the boiler is shut off, freezing temperatures come at an unexpected time, the gas supply gets cut off, or if any part of the boiler is in an outdoor or uninsulated area, there is risk for freezing. Now, if there is glycol mixed in with water, your boiler pipes could face temperatures lower than -54°F and still not freeze.

Using a Boiler with No Glycol or Chemicals

Many small apartments, residences, offices, and churches have boiler systems as part of their HVAC systems. Some of them choose not to use glycol in their boilers. If there is a low chance of the boiler ever freezing, glycol is not necessary. Additional benefits of not using glycol in a boiler for these types of buildings are saving on maintenance labor, water being a more efficient heat transfer conduit, and lower maintenance risks. 

In smaller operations, some facility owners/maintenance managers may choose not to chemically treat their boiler as well. While HVAC boilers are closed-loop and the boiler demand for small buildings is small, chemical treatment will still prolong the life of your boiler.

  • Corrosion inhibitors help prevent rust via a protective film or by modifying the oxygen in the water (“treated glycol” should have corrosion inhibitor mixed in).
  • Scale inhibitors prevent scale by disrupting or dispersing scale-producing molecules.
  • pH balancers add acids or alkaline substances to keep your pH within the manufacturer’s guidelines.
  • Antifoam agents displace surfactants and modify surface tension to prevent foaming.
  • Amines protect against carbonic acid corrosion by neutralizing the acid or forming a protective film layer.

The Benefits of Using Glycol in Boiler Systems

Not Using Glycol?
The main purpose of glycol is its antifreeze properties. Instead of water freezing at 32°F, some glycol mixtures can avoid freezing at temperatures below -54°F.
  • Antifreeze properties– Glycol mixtures can have freeze points at a much lower temperature than that of water, which freezes at 32°F or 0°C. Ethylene glycol is slightly better at freeze protection than propylene. A misconception is that pure glycol has a lower freezing point than water; it needs to mix with water in what is called a “freezing point depression”. For instance, a 60% ethylene glycol and 40% water mixture will not freeze in temperatures colder than -54°F or -48°C.
  • Corrosion resistance– Glycol intended for use in boilers usually comes in a chemical mixture with corrosion inhibitors. Corrosion inhibitors can neutralize corrosion-causing oxygen or form a protective film around the boiler’s metal surfaces. Without this, heat transfer surfaces will have a layer of rust or pitting, which significantly reduces efficiency.

High-Risk Areas for Boiler Loops to Freeze:

Boiler loops are at high-risk in outside areas, especially in colder environments. Loops filled with only water are significantly more vulnerable. Glycol can especially help if your loops are located in any of the following areas:

  • Unconditioned areas
  • No-insulation exterior walls
  • Rooftops/exterior
  • Attics or crawlspaces

Testing Glycol (Glycol Expires)

Expired or diluted glycol is ineffective at preventing freezing or corrosion. Make sure to test annually.

Glycol is an effective antifreeze agent that can protect your HVAC boiler at temperatures below freezing. However, this is only the case if the glycol is not “expired”. You need to test the glycol concentration, iron, and pH annually to ensure it has not degraded. Degraded glycol will provide reduced or no protection against freezing. There are also cases where the glycol may have been diluted over time. For example, if you open the makeup valve and feed in new water without adding a proportional amount of glycol. It is not just freezing that you need to worry about. Treated glycol with corrosion protection will turn into corrosive glycol that will cause rust and pitting in your expensive boiler system.

Boiler Glycol and Chemical Services

Chardon Labs Can Help Treat Your Boiler:
Glycol
Chemicals
Equipment
Testing & Analysis
Automation
Monitoring & Reporting
sales@chardonlabs.com

Chardon Labs can test, feed, and monitor glycol and other chemicals in your boiler system. We can supply and operate the correct equipment to effectively chemically treat it. Protect your investment and remove headaches by reaching out to an expert at Chardon Labs here.

Avatar photo

Matt Welsh

Matt Welsh is the Vice President and Water Consultant at Chardon Labs. He helps consult a wide range of customers utilizing various methods of water treatment, from chemical to chemical-free approaches, large and small applications, and across a wide range of geographical influences. With 20 years of water treatment experience, including a wide range of troubleshooting and service in potable water and non-potable HVAC and industrial applications, he is an expert in water treatment chemistry for cooling towers, boilers, and closed-loop systems.

Previous ArticleClosed-Loop Glycol Replacement and Degradation Next ArticleWhy are Cooling Towers Used in HVAC Systems?